Recent efforts to investigate car-park fires and understand the related mechanisms have fostered the need for analyses of suppression performance against this type of fire scenario. This work aims at providing an insight into the ability of sprinklers and water-mist systems to control and extinguish a fire within an enclosed car park through a series of real-scale experiments. Three cars were employed in each test: the central one was ignited by a heptane pool fire and the adjacent ones served as targets. Two configurations were explored: in the first one, a nozzle was placed directly at the vertical axis of the ignition source, whereas the ignition source was located between the area coverage of four nozzles in the second one. The sprinkler system mainly served as a reference; two values of discharge density were evaluated for water mist at high operative pressure and a biodegradable surfactant was also tested against the most challenging configuration. A quantitative analysis of free-burn and discharge phases by temperature measurements was coupled with radiant heat-flux measurements and an assessment of post-fire damage. Sprinkler and water-mist systems were capable of containing the fire spread and thermally controlling the fire, thus preventing structural damage. The water mist’s ability to overpower the plume and reach the burning surfaces proved more effective than that of sprinklers, especially as no nozzles were located right above the ignition surface. The higher discharge density showed better capability of preventing re-ignition phenomena and suppression was attained in both the investigated configurations, which suggests that a certain amount of flux is also needed to achieve flame cooling. The additive had promising impact on suppression performance; however, more tests are required to specifically explore its ability to enhance thermal control.

Full-scale experiments of fire control and suppression in enclosed car parks: A comparison between sprinkler and water-mist systems / Santangelo, Paolo Emilio; Tarozzi, Luca; Tartarini, Paolo. - In: FIRE TECHNOLOGY. - ISSN 0015-2684. - 52:5(2016), pp. 1369-1407. [10.1007/s10694-016-0569-3]

Full-scale experiments of fire control and suppression in enclosed car parks: A comparison between sprinkler and water-mist systems

SANTANGELO, Paolo Emilio;TARTARINI, Paolo
2016

Abstract

Recent efforts to investigate car-park fires and understand the related mechanisms have fostered the need for analyses of suppression performance against this type of fire scenario. This work aims at providing an insight into the ability of sprinklers and water-mist systems to control and extinguish a fire within an enclosed car park through a series of real-scale experiments. Three cars were employed in each test: the central one was ignited by a heptane pool fire and the adjacent ones served as targets. Two configurations were explored: in the first one, a nozzle was placed directly at the vertical axis of the ignition source, whereas the ignition source was located between the area coverage of four nozzles in the second one. The sprinkler system mainly served as a reference; two values of discharge density were evaluated for water mist at high operative pressure and a biodegradable surfactant was also tested against the most challenging configuration. A quantitative analysis of free-burn and discharge phases by temperature measurements was coupled with radiant heat-flux measurements and an assessment of post-fire damage. Sprinkler and water-mist systems were capable of containing the fire spread and thermally controlling the fire, thus preventing structural damage. The water mist’s ability to overpower the plume and reach the burning surfaces proved more effective than that of sprinklers, especially as no nozzles were located right above the ignition surface. The higher discharge density showed better capability of preventing re-ignition phenomena and suppression was attained in both the investigated configurations, which suggests that a certain amount of flux is also needed to achieve flame cooling. The additive had promising impact on suppression performance; however, more tests are required to specifically explore its ability to enhance thermal control.
2016
52
5
1369
1407
Full-scale experiments of fire control and suppression in enclosed car parks: A comparison between sprinkler and water-mist systems / Santangelo, Paolo Emilio; Tarozzi, Luca; Tartarini, Paolo. - In: FIRE TECHNOLOGY. - ISSN 0015-2684. - 52:5(2016), pp. 1369-1407. [10.1007/s10694-016-0569-3]
Santangelo, Paolo Emilio; Tarozzi, Luca; Tartarini, Paolo
File in questo prodotto:
File Dimensione Formato  
Full-Scale Experiments of Fire Control.pdf

Accesso riservato

Descrizione: Article in press
Tipologia: Versione pubblicata dall'editore
Dimensione 24.56 MB
Formato Adobe PDF
24.56 MB Adobe PDF   Visualizza/Apri   Richiedi una copia
Santangelo_FT_2016_Pre-production.pdf

Open access

Tipologia: Versione dell'autore revisionata e accettata per la pubblicazione
Dimensione 1.71 MB
Formato Adobe PDF
1.71 MB Adobe PDF Visualizza/Apri
Pubblicazioni consigliate

Licenza Creative Commons
I metadati presenti in IRIS UNIMORE sono rilasciati con licenza Creative Commons CC0 1.0 Universal, mentre i file delle pubblicazioni sono rilasciati con licenza Attribuzione 4.0 Internazionale (CC BY 4.0), salvo diversa indicazione.
In caso di violazione di copyright, contattare Supporto Iris

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11380/1108400
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 22
  • ???jsp.display-item.citation.isi??? 21
social impact