Non-linear loads such as AC drives switch-mode power supplies and grid-connected converters can cause, besides the generation of unwanted current harmonics, a DC current component injection into the grid. This DC current component can lead to magnetic saturation of the distribution power transformers, leading to higher current distortion and overheating. This paper presents a method to detect the DC current component flowing into the distribution power transformer with a precise measurement of the DC voltage component at the transformer winding. A magnetic sensor has been developed and implemented in a closed-loop control system to achieve a high sensitivity and guarantees a good linearity with a high rejection ratio to grid voltage variations. Simulation and experimental results confirm the effectiveness of the proposed approach.

Detection Method of the DC bias in Distribution Power Transformers / G., Buticchi; Lorenzani, Emilio. - In: IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS. - ISSN 0278-0046. - STAMPA. - 60:(2013), pp. 3539-3549. [10.1109/TIE.2012.2226418]

Detection Method of the DC bias in Distribution Power Transformers

LORENZANI, EMILIO
2013

Abstract

Non-linear loads such as AC drives switch-mode power supplies and grid-connected converters can cause, besides the generation of unwanted current harmonics, a DC current component injection into the grid. This DC current component can lead to magnetic saturation of the distribution power transformers, leading to higher current distortion and overheating. This paper presents a method to detect the DC current component flowing into the distribution power transformer with a precise measurement of the DC voltage component at the transformer winding. A magnetic sensor has been developed and implemented in a closed-loop control system to achieve a high sensitivity and guarantees a good linearity with a high rejection ratio to grid voltage variations. Simulation and experimental results confirm the effectiveness of the proposed approach.
2013
60
3539
3549
Detection Method of the DC bias in Distribution Power Transformers / G., Buticchi; Lorenzani, Emilio. - In: IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS. - ISSN 0278-0046. - STAMPA. - 60:(2013), pp. 3539-3549. [10.1109/TIE.2012.2226418]
G., Buticchi; Lorenzani, Emilio
File in questo prodotto:
File Dimensione Formato  
Detection Method of the DC Bias in Distribution.pdf

Accesso riservato

Descrizione: Articolo principale
Tipologia: Versione pubblicata dall'editore
Dimensione 2.66 MB
Formato Adobe PDF
2.66 MB Adobe PDF   Visualizza/Apri   Richiedi una copia
Pubblicazioni consigliate

Licenza Creative Commons
I metadati presenti in IRIS UNIMORE sono rilasciati con licenza Creative Commons CC0 1.0 Universal, mentre i file delle pubblicazioni sono rilasciati con licenza Attribuzione 4.0 Internazionale (CC BY 4.0), salvo diversa indicazione.
In caso di violazione di copyright, contattare Supporto Iris

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11380/853292
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 48
  • ???jsp.display-item.citation.isi??? 37
social impact