Non-linear loads such as AC drives switch-mode power supplies and grid-connected converters can cause, besides the generation of unwanted current harmonics, a DC current component injection into the grid. This DC current component can lead to magnetic saturation of the distribution power transformers, leading to higher current distortion and overheating. This paper presents a method to detect the DC current component flowing into the distribution power transformer with a precise measurement of the DC voltage component at the transformer winding. A magnetic sensor has been developed and implemented in a closed-loop control system to achieve a high sensitivity and guarantees a good linearity with a high rejection ratio to grid voltage variations. Simulation and experimental results confirm the effectiveness of the proposed approach.
Detection Method of the DC bias in Distribution Power Transformers / G., Buticchi; Lorenzani, Emilio. - In: IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS. - ISSN 0278-0046. - STAMPA. - 60:8(2013), pp. 3539-3549. [10.1109/TIE.2012.2226418]
Detection Method of the DC bias in Distribution Power Transformers
LORENZANI, EMILIO
2013
Abstract
Non-linear loads such as AC drives switch-mode power supplies and grid-connected converters can cause, besides the generation of unwanted current harmonics, a DC current component injection into the grid. This DC current component can lead to magnetic saturation of the distribution power transformers, leading to higher current distortion and overheating. This paper presents a method to detect the DC current component flowing into the distribution power transformer with a precise measurement of the DC voltage component at the transformer winding. A magnetic sensor has been developed and implemented in a closed-loop control system to achieve a high sensitivity and guarantees a good linearity with a high rejection ratio to grid voltage variations. Simulation and experimental results confirm the effectiveness of the proposed approach.File | Dimensione | Formato | |
---|---|---|---|
Detection Method of the DC Bias in Distribution.pdf
Accesso riservato
Descrizione: Articolo principale
Tipologia:
VOR - Versione pubblicata dall'editore
Dimensione
2.66 MB
Formato
Adobe PDF
|
2.66 MB | Adobe PDF | Visualizza/Apri Richiedi una copia |
Pubblicazioni consigliate
I metadati presenti in IRIS UNIMORE sono rilasciati con licenza Creative Commons CC0 1.0 Universal, mentre i file delle pubblicazioni sono rilasciati con licenza Attribuzione 4.0 Internazionale (CC BY 4.0), salvo diversa indicazione.
In caso di violazione di copyright, contattare Supporto Iris